How do you extinguish a lithium-ion battery fire safely?

To extinguish a lithium-ion battery fire safely, apply a large volume of a cooling agent, ideally a purpose-designed one such as Hydrogel, directly to the battery. Keep applying it until no visible flames remain, no new eruptions occur, and audible gas emissions have stopped. Water can suppress visible flames, but it does not always keep the battery cool enough to prevent reignition, particularly where it cannot reach cells inside an enclosed pack. Suppressing flames is not the same as stabilising the battery: internal heating and gas release can continue after the fire appears to be out. The sections below cover the most important questions about lithium-ion battery fire safety, from why these fires behave differently to what you should avoid during an incident.

Why are lithium-ion battery fires so difficult to extinguish?

Lithium-ion battery fires are difficult to extinguish because the energy sustaining them comes from chemical reactions inside the cells, not from an external fuel source. Visible flames can be suppressed while the internal reaction continues. The cells keep releasing heat, flammable gas, and pressure, and the fire can reignite minutes or even hours later.

The core problem is thermal runaway. When a lithium-ion cell is damaged, overheated, or improperly charged, its internal materials begin to decompose. Temperature rises, flammable gases such as hydrogen and methane are released, internal pressure builds, and the casing can rupture. Heat from the failing cell then transfers to neighbouring cells and can trigger a cascade of failures across the pack. Temperatures during thermal runaway can be very high, which makes the fire hard to approach and control.

Three further factors add to the challenge:

  • Toxic gases. Hydrogen fluoride, which is toxic and corrosive, can be released during the incident and may persist after flames have disappeared.
  • Limited reach. Water, foam, and powder can suppress surface flames. However, an agent applied from outside may not reach cells inside an enclosed pack, so it may not stop the internal reaction.
  • Self-sustaining reaction. Some cell chemistries release oxygen as they decompose, so the fire can continue without an external oxygen supply.

What are the safest methods to extinguish a lithium-ion battery fire?

The safest approach is to apply a large volume of a cooling agent designed for battery fires. The agent should lower battery temperature rapidly and stay in contact with the battery surface to keep cooling it. Maintain a safe distance, wear respiratory protection, and keep monitoring the battery after visible flames are suppressed.

The application procedure matters as much as the agent. An effective sequence is:

  1. Apply the extinguishing agent in controlled intervals to maintain a consistent cooling layer on the battery surface.
  2. Direct the stream toward visible flames and areas where gas is being released.
  3. Once flames are controlled, focus application on the battery pack surface.
  4. Where the pack design allows, deliver the agent to the areas where heat is concentrated. Access to internal cells depends on the enclosure and battery configuration.
  5. Monitor for renewed gas emissions, new flame eruptions, and signs of thermal runaway spreading to adjacent cells.
  6. Repeat targeted application wherever flames re-emerge.

Treat a battery as stabilised only when no visible flames remain, no new eruptions occur, and audible gas emissions such as hissing or sizzling have stopped. Keep monitoring even then, because residual heat and chemical activity can persist after the fire appears to be out.

Operators must wear appropriate respiratory protection throughout the intervention. Even with an effective agent, hazardous gases are reduced, not eliminated. The exposure risk remains until the battery has fully cooled and gas emissions have ceased.

See where Hydrogel fits your fire-safety strategy
From lithium-ion batteries to existing water-based suppression systems, speak with Anogas about your application.

Discuss your application

What type of fire extinguisher works on lithium-ion batteries?

Extinguishers designed for lithium-ion battery fires are the appropriate choice. These use a large-volume cooling agent that stays in contact with the battery surface. Dry powder, CO₂, and conventional foam extinguishers can knock down flames. However, they provide little or no sustained cooling, so they are not suited to stopping thermal runaway or preventing reignition.

Hydrogel is a water-based agent containing modified natural clay. It cools the battery rapidly, and its viscosity responds to heat: it thickens on contact with hot surfaces. This is intended to keep the agent on the battery instead of running off, which is a limitation of water alone. It also helps isolate the battery thermally and reduce the release of gases. How far it reaches into an enclosed pack depends on access, battery configuration, and how the agent is delivered. It does not guarantee that reignition will not occur.

Hydrogel products have distinct roles. Hydrogel provides cooling and initial fire suppression. Hydrogel Shield is intended for longer-term containment, to help prevent reignition of damaged or extinguished batteries. Hydrogel SubZ is a frost-protected formulation for relevant cold-temperature applications.

As an indicative guide, at least 2 litres of Hydrogel is a typical starting quantity for small devices such as smartphones and laptops. For medium systems such as e-bikes and power tools, at least 6 litres is typical. Treat these figures as application-specific. The quantity required depends on the battery, its enclosure, and how the agent is delivered. Larger industrial installations need significantly greater volumes and should be assessed individually. Handheld fire extinguishers using Hydrogel are available for portable use in warehouses, workshops, and public spaces where battery fire risk is present.

Hydrogel has been tested to KIWA NTA 8133 for lithium-ion battery fire applications. That test applies to a specific extinguisher model and test scope. It is not approval for every battery size, application, or installed system. Verify the scope of any certificate against your own application. Hydrogel is also PFAS-free, which matters as European regulation moves toward restricting PFAS-containing extinguishing agents.

How does thermal runaway spread to other battery cells?

Thermal runaway spreads through heat transfer. When one cell reaches a critical temperature, the heat it generates conducts to adjacent cells and raises their temperature until they also enter thermal runaway. The result is a cascading failure that can engulf an entire pack even if only one cell was initially compromised.

Propagation follows a clear pattern. A failing cell decomposes internally, releasing flammable gases and intense heat. That heat reaches neighbouring cells through direct conduction and through hot gases accumulating inside the enclosure. When a neighbouring cell reaches its own threshold, it begins the same process and passes heat to the next cell in the sequence.

This is why thermal isolation is one of the most important functions of a battery fire suppression agent. An agent that forms a barrier around affected cells and limits heat transfer can interrupt the cascade before it spreads across the pack. Hydrogel is designed to do this where it can reach the cells. Its gel layer restricts heat transfer and helps separate escaping gases from potential ignition sources.

In large installations such as energy storage systems, cascading thermal runaway is a particular risk because the number of cells and the stored energy are much greater. In these cases, suppression from a safe distance may be needed to contain the fire until emergency services arrive, instead of attempting full extinguishment immediately.

What should you never do when a lithium-ion battery catches fire?

Do not rely on a standard dry powder or CO₂ extinguisher as your primary strategy, do not assume the fire is out once visible flames disappear, and do not approach the battery without respiratory protection. Each of these mistakes can cause serious injury or allow the fire to reignite.

The most dangerous assumption is that a suppressed fire is a finished one. Thermal runaway can continue internally after visible flames are extinguished. A battery that looks safe may still be generating heat, releasing toxic gases, and building toward reignition. Treating the incident as resolved too early is one of the most common and serious errors in battery fire response.

Other actions to avoid:

  • Using too little extinguishing agent. Insufficient cooling allows the battery to reheat quickly. Large volumes are needed to bring battery temperature down to a safe level.
  • Moving a burning or recently burned battery without precaution. Physical disturbance can accelerate gas release or trigger reignition in cells that have not yet fully failed.
  • Sealing a burning battery in an enclosed space without ventilation. Gas accumulation in a sealed space creates an explosion risk.
  • Ignoring gas emissions after flames are suppressed. Hissing, sizzling, or visible vapour means the battery is still active and potentially dangerous.
  • Assuming a suppressed battery is safe to store, transport, reuse, or dispose of. Extinguishment does not make a damaged battery safe to handle.

How long does it take for a lithium-ion battery fire to be fully safe?

A lithium-ion battery fire is not fully safe until the battery has cooled to a stable temperature, all gas emissions have ceased, and no new flames have appeared over a sustained monitoring period. This can take several hours, and considerably longer for large battery systems. Continued monitoring is essential after active suppression ends.

There is no universal timeframe. Cooling time depends on the size of the battery, the volume of agent applied, ambient conditions, and whether the agent provides sustained cooling or only a brief drop in surface temperature. A smartphone battery in a minor incident may stabilise within an hour under proper cooling. A large EV battery pack or energy storage system may need many hours of sustained cooling and monitoring before it is safe to approach.

The stabilisation criteria that matter most are practical, not time-based:

  • No visible flames remain.
  • No new flame eruptions occur after suppression.
  • Audible gas emissions (hissing, sizzling, or popping) have stopped.
  • The battery surface temperature has dropped to a level that no longer poses a reignition risk.

Agents that keep cooling after application, such as Hydrogel, which adheres to hot surfaces and continues absorbing heat, can reduce the need for constant reapplication. Even so, treat the battery as potentially hazardous until emergency services have assessed it and confirmed it is safe. Where longer-term containment of a damaged battery is needed, assess whether Hydrogel Shield suits the situation.

If you are responsible for fire safety where lithium-ion batteries are present, such as warehouses, EV charging facilities, recycling centres, or industrial sites, plan for extended post-suppression monitoring. Do not assume a quick resolution. If you are evaluating battery fire suppression systems for a fixed installation, assess the complete setup: access to the battery, enclosure design, agent quantity, nozzle and discharge arrangement, coverage, operating temperature, and the approvals required. Do not assume an existing sprinkler system will work with Hydrogel, and do not modify mandatory fire protection without engineering and approval checks. The cooling persistence of the agent is one of the most important performance criteria to compare.