Using a conventional water-based fire extinguisher on live electrical equipment is dangerous and should be avoided. Plain water conducts electricity, so the stream can carry current back to the operator and cause electrocution. However, not every water-based agent carries the same risk. Formulation, viscosity and application method all determine whether a water-based suppressant can be used safely near energised equipment. The sections below work through the key questions fire safety professionals ask when evaluating suppression options for electrical hazards.
What makes water dangerous on electrical fires?
Plain water is dangerous on electrical fires because it conducts electricity. When a water stream contacts energised equipment, it creates a conductive path between the live source and the person holding the extinguisher. The risk rises with the continuity of the stream. A solid jet is far more hazardous than a fine mist or a gel that does not flow freely.
Electrical current follows the path of least resistance, and a continuous column of tap water provides exactly that. Voltage, distance and stream type all influence the severity of the shock hazard. At low voltages and with sufficient standoff distance, the risk may be manageable. At mains voltage or above, an unbroken water jet can be lethal.
A secondary hazard is thermal shock. When water hits overheated electrical components, it can vaporise rapidly, scattering burning debris and potentially spreading the fire. For these reasons, standard fire safety guidance has long excluded plain water from use on live electrical equipment. Most jurisdictions treat such fires separately and require specifically rated agents.
Are all water-based agents equally risky on live equipment?
No. The conductivity of a water-based agent depends on its formulation, not just its water content. Agents that are highly viscous, gel-forming or applied as a foam present a lower conductivity risk than plain water. The absence of a continuous liquid stream interrupts the electrical circuit between the equipment and the operator. Lower risk is not the same as proven safety, though. Each agent still needs to be tested.
This distinction matters for modern fire safety planning. Many facilities are reviewing dry powder and CO₂ extinguishers because of cleanup costs, environmental impact and their limited cooling effect on lithium-ion battery fires. A water-based agent engineered and tested for use near electrical equipment can fill part of this gap. It must first be independently verified against the relevant dielectric requirements at a defined voltage and standoff distance.
Key variables that determine electrical safety in water-based agents include:
- Viscosity and gel formation: Agents that thicken on contact with heat, or that are applied as a foam, do not form a continuous conductive stream
- Mineral ion content: Dissolved salts and minerals increase conductivity; deionised or clay-based formulations can reduce it
- Application method: Spray nozzles that break the stream into droplets reduce conductivity compared with solid jets
- Standoff distance: Greater distance between nozzle and equipment reduces the risk, even for agents with some residual conductivity
Certification testing, typically dielectric breakdown tests at defined distances and voltages, is the reliable way to confirm whether a specific agent is suitable for use near energised equipment. Do not use agents that have not been tested and rated for this purpose on live electrical fires, however they are marketed.
How does Hydrogel behave differently from water on electrical equipment?
Hydrogel is a water-based agent containing modified natural clay. Its heat-responsive viscosity is designed to stop it forming a continuous conductive stream. Applied near heat, the low-viscosity fluid thickens into a gel that adheres to hot surfaces instead of running off. This interrupts the conductive path that makes plain water hazardous near live equipment. Hydrogel can be used on electrical equipment up to 1,000 V when applied with suitable nozzle configurations. Confirm the test evidence, voltage rating and nozzle arrangement for your specific application before relying on this.
The clay gives the agent its heat-responsive behaviour. At ambient temperatures, the fluid is thin enough to be pumped through water-based suppression systems. On contact with hot surfaces, it thickens into a viscous gel that stays in place. This keeps the agent in contact with the heat source and improves cooling compared with plain water, which tends to run off or pool.
This behaviour also matters for lithium-ion battery fires. Extinguishing visible flames does not necessarily end internal heating, gas release or thermal runaway, and reignition can follow apparent extinguishment. A gel layer that stays on external battery surfaces supports sustained cooling. Its effect depends on access to the battery, the pack and enclosure design, and how the agent is delivered. An externally applied agent cannot be assumed to reach cells inside an enclosed pack. Hydrogel is intended for cooling and initial fire suppression. It does not guarantee that reignition will not occur. Keep monitoring the battery after the fire, as residual heat and gas hazards can persist. For a detailed breakdown of how the mechanism works, see the Hydrogel mechanism page.
Hydrogel contains no PFAS and is classified as non-dangerous for humans and the environment under European chemical regulations. This is relevant when the agent is used indoors or near drainage systems. It is a statement about composition and classification, not about firefighting performance.
What fire classes cover electrical equipment fires?
Electrical equipment fires do not have a universally standardised fire class across all regulatory frameworks. In Europe, electrical fires are sometimes called Class E fires informally. EN 2, the European standard that defines Classes A, B, C, D and F, does not define such a class. In practice, most European countries specify that an extinguisher has been tested and rated for use on live electrical equipment at a defined voltage, rather than assigning a class letter.
In the United States, Class C covers fires involving energised electrical equipment, and agents rated for Class C use must demonstrate non-conductivity. Australia and some other jurisdictions use the letter E explicitly. Fire safety managers operating across borders should check the specific certification claims of any agent they evaluate, rather than relying on a class letter alone.
The frameworks share one principle. An agent used on live electrical equipment must not create a conductive path back to the operator, and this must be demonstrated through standardised dielectric testing rather than assumed from the agent’s general properties. Verify two figures: the voltage at which the agent was tested and the standoff distance used in that test.
Which extinguishing agents are approved for use near electrical equipment?
The agents most commonly used near live electrical equipment are CO₂, dry powder, clean agents and certain water-based agents that have passed dielectric testing. CO₂ is non-conductive and leaves no residue, which makes it a traditional choice for server rooms and switchgear. Dry powder is effective but can cause significant collateral damage to sensitive equipment and creates respiratory hazards. Water-based agents are suitable only when their specific formulation and application method have been independently tested and certified at the relevant voltage.
Each option involves trade-offs:
- CO₂: Non-conductive and residue-free, but provides limited cooling for battery fires and poses an asphyxiation risk in enclosed spaces
- Dry powder: Effective on many fire types, but can damage equipment, is difficult to clean up, and provides little sustained cooling for lithium-ion battery fires
- Halon alternatives (clean agents): Effective and residue-free, but typically expensive and, depending on the agent, subject to environmental restrictions
- Certified water-based agents: Capable of sustained cooling and flame suppression, and increasingly available in PFAS-free formulations, but suitable only where dielectric testing confirms safety at the relevant voltage
Where lithium-ion battery risks exist, such as EV charging points, energy storage systems and industrial battery banks, consider whether the agent provides sustained cooling. CO₂ and dry powder are effective at suppressing flames but do little to address continued heating or thermal runaway, so reignition remains a risk. A thermal runaway blocker combines sustained cooling with flame suppression and is designed to help limit reignition. Confirm the suitability of any agent against the voltage rating, battery configuration and application scenario before deployment.
Should fire safety managers switch to PFAS-free water-based agents?
Fire safety managers have strong practical and regulatory reasons to evaluate PFAS-free water-based agents now. European regulation is phasing out PFAS-containing extinguishing agents under Regulation (EU) 2025/1988, with a complete ban expected by 2031. Facilities still using PFAS-based foams face a compliance deadline and growing liability from environmental contamination. Moving to a certified PFAS-free alternative ahead of the deadline reduces regulatory risk and avoids emergency procurement under pressure.
The performance question also deserves attention. PFAS-based foams were valued for their film-forming properties, which let them spread quickly across fuel surfaces. PFAS-free formulations, including gel-based agents, work through different mechanisms such as sustained adhesion, thermal insulation and cooling. For lithium-ion battery fires, film-forming agents offer limited benefit against internal thermal runaway, and a cooling-focused, gel-based approach suits the hazard better. Compare test evidence for the specific hazard rather than assuming equivalence.
Water-based agents that are interchangeable with water can often be integrated into existing suppression infrastructure. Fixed fire suppression systems designed for water-based agents may be adaptable without replacing pipework, nozzles or control systems. Do not assume an existing sprinkler system works with Hydrogel. Check agent quantity, nozzle and discharge arrangement, coverage, temperature rating, compatibility and any required approvals first. Handheld extinguishers filled with PFAS-free Hydrogel can replace conventional units, subject to the same checks on ratings and approvals. Do not modify mandatory fire protection without engineering and approval review.
Base the decision on three factors: the fire risks present in the facility, the voltage and configuration of the electrical equipment involved, and the regulatory timeline in your jurisdiction. For facilities managing lithium-ion battery risks alongside electrical equipment, a PFAS-free, dielectrically tested water-based agent can address both concerns in one product. Hydrogel is not a universal solution and should sit within the wider fire-safety response. The Hydrogel product page provides technical specifications for fire safety managers evaluating this transition.