Hydrogel is a water-based extinguishing agent containing modified natural clay. It is designed to cool burning surfaces and suppress fire by thickening as it heats, so that it stays in contact with hot surfaces instead of running off. This makes it relevant to lithium-ion battery fires, where sustained cooling matters and where water and foam agents can struggle to keep surfaces cool. The sections below explain how Hydrogel works, where it applies, and what to check before specifying it.
How does hydrogel actually extinguish a fire?
Hydrogel works mainly through cooling and surface adhesion. Its high water content absorbs heat quickly. Its clay-based structure becomes more viscous as temperatures rise, which is intended to keep the agent on hot surfaces and maintain cooling for longer than plain water can.
Extinguishing visible flames is not the same as stabilising a battery. In a lithium-ion battery, internal heating, gas release and thermal runaway can continue after the flames are out, and reignition remains possible. Cooling is therefore the central objective, and it is the reason adhesion matters: it keeps the agent working on the surface for longer.
The gel layer also forms a partial barrier that can restrict oxygen at the surface and help separate escaping flammable gases from ignition sources. How far this helps depends on how the agent is applied and how the battery is built. An externally applied agent cannot be assumed to reach cells inside an enclosed pack or to stop every internal reaction. Performance depends on access to the battery, battery configuration, delivery of the agent and the available test evidence.
This is what sets hydrogel fire suppression apart from agents that offer only brief surface cooling: it combines cooling with persistence on the hot surface. It does not replace a proper post-fire response.
What makes hydrogel different from water and foam agents?
The key difference is persistence. Water runs off hot surfaces quickly, which reduces its cooling efficiency and can mean large volumes are needed. Foam provides a surface barrier but cools less effectively, and many foams contain PFAS, which carry environmental and regulatory risks. Hydrogel combines the cooling capacity of water with an adhesive, heat-responsive structure that stays in contact with the fire source for longer.
Each agent has a role. Water is effective for cooling, foam suppresses many liquid fuel fires, and CO2 and dry chemical systems have their own uses. Their limits show up in lithium-ion battery fires, where thermal activity can persist beneath the surface and agents that drain away or only blanket the flames may not maintain cooling. Hydrogel’s sustained adhesion is an advantage in that situation.
Because the agent stays in place, less of it may be needed to achieve a given result. That can reduce runoff and post-incident waste, although the quantity required depends on the fire, the equipment involved and how the agent is delivered.
Lithium-ion cells can release hydrogen, methane and hydrogen fluoride during thermal runaway. Hydrogel is designed to interact with hydrogen fluoride and convert it into less harmful ionic components. This reduces the hazard but does not eliminate it, and appropriate respiratory protection remains essential for anyone near the incident.
The product is PFAS-free, consists of more than 99% natural components and has a low carbon footprint. Its service life is typically more than ten years, and the material is expected to be recyclable as a compost-enrichment supplement at end of life. These are environmental characteristics. They do not by themselves demonstrate firefighting performance or approval for a particular application.
What types of fires can hydrogel suppress?
Hydrogel is rated for Class A, Class B and Class F fires, covering solid combustibles, flammable liquids and cooking oils respectively. It is also designed for lithium-ion battery fires, which fall outside the standard fire classes.
Class A coverage includes wood, paper, textiles and plastics, the most common fuels in buildings, warehouses and industrial environments. The gel’s adhesion to vertical surfaces and its sustained cooling help it stay effective where water would run off before removing enough heat.
For Class B fires involving flammable liquids, Hydrogel floats on non-polar fuels and fats, forming a layer that restricts vapour release and limits reignition. Class F coverage addresses cooking oil fires, which burn at very high temperatures and can reignite violently if cooled too quickly with plain water.
Lithium-ion battery fires are the most technically demanding application. They involve thermal runaway, a self-sustaining chain reaction in which heat from one failing cell triggers neighbouring cells, releasing flammable and toxic gases. Hydrogel is designed to cool the battery surface, insulate it and reduce gas hazards. Its effectiveness depends on whether the agent can reach the affected cells, and it should be assessed against the battery configuration and the available test evidence. The thermal runaway blocker application is intended to help interrupt propagation through a battery pack. Whether it does so in a given installation depends on access, agent quantity and delivery.
Longer-term containment is a separate role. Hydrogel Shield is intended to help prevent reignition of damaged or extinguished batteries, while Hydrogel handles cooling and initial suppression. Hydrogel SubZ is a frost-protected formulation for relevant cold-temperature applications.
Is hydrogel safe for people and the environment?
Hydrogel is classified as non-dangerous for humans and the environment under European chemical legislation. It is made from modified clay and water, contains no PFAS, and has been tested for aquatic toxicity against algae and daphnia according to OECD guidelines, with results indicating it is non-toxic to aquatic life. PFAS-free status is based on analytical testing, which shows that PFAS were not detected rather than proving absolute absence. It is also a separate claim from environmental safety or firefighting performance.
Standard safety precautions still apply when operators apply Hydrogel to a live fire. Lithium-ion battery fires release hazardous gases, including hydrogen fluoride, whichever agent is used. Hydrogel is designed to reduce the concentration of these gases and to convert hydrogen fluoride into less harmful compounds, but it does not remove the exposure risk. Respiratory protection and a safe working distance remain necessary.
The post-fire period needs attention as well. Residual heat, gas hazards and the risk of reignition can persist after a battery fire appears controlled. Plan for monitoring, restricted access and safe handling. Extinguishment does not make a battery safe to reuse, store, transport or dispose of.
Because Hydrogel adheres to surfaces longer than water, less agent may be needed per incident, which can mean less contaminated runoff reaching drains or soil. After use, residual hydrogel can be removed by absorbing excess material and rinsing with water. The material can be collected and recycled, and its clay components may be suitable for reuse as compost enhancers.
Can hydrogel be used in existing fire suppression systems?
Hydrogel is designed to be interchangeable with water in water-based fire suppression systems. In principle, this means sprinkler systems, fixed installations and handheld extinguishers that currently use water can be adapted without replacing pipework, nozzles or storage tanks. Do not assume that an existing system will work with Hydrogel. Verify compatibility with the system manufacturer and the relevant approval route first.
Assess the complete firefighting setup. Check access to the battery, enclosure design, agent quantity, nozzle and discharge arrangement, coverage and operating temperature. Hydrogel should not replace mandatory fire protection, and systems should not be modified without engineering and approval checks. This applies especially in marine settings, where flag-state requirements, class rules and marine equipment approvals each apply separately.
Hydrogel has also been shown to be suitable for electrical equipment up to 1,000 V when used with appropriate nozzle configurations. This is relevant to data centres, EV charging infrastructure and industrial facilities where electrical hazards are present alongside fire risk. Confirm the voltage limit and nozzle requirements for the specific application.
For fixed fire suppression systems, compatibility with water-based infrastructure can reduce the effort of upgrading protection for lithium-ion battery storage, warehouses, energy storage installations and recycling facilities. For portable use, handheld hydrogel extinguishers are available for first response where a fixed system may not cover every risk zone.
When discussing certification, identify the specific extinguisher model, test and scope. A passed portable-extinguisher test, such as NTA 8133 or EN 3-11, is not approval of every model, battery size or installed system. Verify whether a certificate has been granted or is still pending before relying on it.
Hydrogel has a service life of more than ten years, so systems charged with the agent should not need early replacement for technical reasons. When replacement is eventually needed, check local discharge and waste requirements before disposal.
Where is hydrogel fire suppression currently being used?
Hydrogel fire suppression is applied in industries where lithium-ion battery risk and PFAS regulation overlap. Adoption in 2026 is most active in warehousing and logistics, maritime operations, recycling facilities and energy storage installations. All of these sectors face growing fire risk from battery-powered equipment and increasing pressure to move away from PFAS-based agents.
In warehousing and logistics, e-bikes, power tools and battery-powered handling equipment concentrate fire risk in ways that standard sprinkler water systems may address only partially. Hydrogel is intended to help suppress lithium-ion battery fires and limit thermal runaway propagation. Facilities that store or charge batteries at scale should assess whether it suits their layout and charging arrangements.
Maritime applications can benefit from Hydrogel’s persistence, as less agent may be needed than with water alone, which matters where storage space and weight are constrained. Marine use still depends on flag-state requirements, class rules and marine equipment approvals, and portable-extinguisher test results do not amount to approval of a complete marine battery installation. Recycling facilities handling electronic waste and end-of-life batteries are another high-risk setting, where Hydrogel’s gas-reduction properties add protection for workers.
At the portable level, Hydrogel extinguishers are used in commercial buildings, industrial plants and public spaces where a first-response tool for multiple fire classes, including battery fires, is valuable. Anogas supplies these products through a network of fire safety partners across Europe and beyond. For technical specifications, verified capabilities and application guidance, see the Hydrogel product page.